Handoff: aska-physical/optifab v0.3.3
Written under the group ethos: leave everything the next agent needs so nothing has to be derived twice.
optifab v0.1.0, v0.2.0 and v0.3.0 were prepared by an AI agent on 2026-11-17, and v0.3.1 on 2026-11-24. They are claimed work. No person has
reviewed them.
1. What was learned and checked
The aim, stated by the owner and in issue 1, is one
physical structure that holds all four organisations’ work, with digital and physical infrastructure as a
single unit. docs/STRUCTURE.md is the design of that unit as far as it can be checked today.
The findings are in README.md and derived in docs/MODEL.md. In one line each:
- The 3.06 MW of utility power that funi-frame’s plant frees carries 2.85 to 2.96 MW of IT load, depending on
how much of the overhead grows with load. Adopted in funi-frame v0.1.1.
- The sorption stage needs a heat sink below 41.5 °C at best to reach its claimed COP. funi-frame v0.1.0 had
no recooling temperature. v0.1.1 carries the limit and a proposed design value of 30 °C.
- The campus stops cooling itself below about 0.56 MW of IT load. A worse wall raises that floor.
- The PCM skid is a budget of 2,500 kWh_th that outages and bursts draw on.
- The tightest certified margin in the building is the floor punching collar, at 80.1%.
- Weft’s gate predicate, rewritten here, passes Weft’s 15 weight-update vectors, agrees with Weft’s own
function on 100,000 generated cases, and can take the plant’s budget and margin radius as its inputs.
- Six hand-copied values across three repositories agree and are now under test.
- The four organisations’ relevant work is one cited graph of 41 repositories and 43 links.
- The physical stack is at “claimed” on the Ledger scale, with one preprint.
- The contract’s whole state fits the 64-byte frame Weft uses for telemetry.
- The Terrafab latency figures hold in direction for the plant’s vibration tones, and the campus as designed
does not need a fast loop.
- 32 of 41 repositories have a place in the structure. Of the 10 interfaces that would close the loop between
structure and intelligence, 4 are checked, and the loop is open in three places.
- An exact integer gate and the loop built on it are proved in Lean (eight theorems, six kernels, standard
axioms). The Proven Commons bar check passes items 2 to 6. Item 1, a reviewer’s approval, is open.
- A loop changed three hardware and two software parameters together under that gate: 45 of 48 proposals
admitted, the objective up from 0.914210 to 0.918990, every decision replayed in Lean.
- A design that sits exactly on a limit cannot change under this gate, and a proposer with no reserve slows
itself.
- v0.3.0: the plant model, the bounds, the objective and the step are in Lean beside the gate, and seven more
theorems are about designs (fifteen in all, sixteen since v0.3.1). For any proposer the design held stays within the model’s
limits and its bounds, its objective never falls, and a margin within the limit is proved to mean three
exact inequalities about heat and storage.
- A language model proposed through
tools/propose.py, seeing only the printed state: 12 proposals, 7
taken up, objective 0.919529, the best a direct search finds possible (the seeded search reached 89.9% of
that gain). A second instance of the same model, given the first run’s notes, reached 0.919529 in 5.
Two runs, not an experiment. Both runs end with the load_floor margin at 999,215 ppm, 785 from its limit.
- 3,007 adversarial proposals could not move the design out of its envelope or past its budget.
- Under assumption A-4 the load floor rises steeply with recooling temperature: 0.564 MW at 30 °C,
2.804 MW at 38 °C, no self-cooling at 41 °C. Placement between campuses is degenerate in the
current plant model.
- v0.3.1 corrected two mistakes in the plant model that an independent read had found: the objective’s
outage term and the outage margin, which left out the fixed heat load. Do not carry a recorded run across a
change to the model. Only 2 of the 15 proposals recorded against v0.3.0 are decided the same way
under v0.3.1, so both runs were made again and the old ones are in
results/v0.3.0/.
docs/VISION.md sets these against the vision, part by part.
2. Negative findings. Do not re-derive.
- There is no energy data on the digital side. A search of Weft’s runtime, documents and papers, and of
weft-loom’s experiments and notes, finds no figure in watts, joules or kWh and no PUE. Weft’s only
temperature is a formula of CPU load (
weft/runtime/telemetry/host_metrics.py:45). weft-loom lists “energy
per adapter write” as a measurement still to make. exo-os quotes small-device power figures from outside
sources under the line “Do not trust any mW number without a test.” So tokens per joule, or energy per model
update, cannot be computed from anything the four organisations hold today. It has to be measured.
- One lattice link is closed, and the others are only proposals. incentre-lattices, fibral-rigidity and
siliquant all work with lattices, which suggests a shared result. siliquant checked whether the certificate
coefficients of incentre-lattices bear on weight rounding and recorded “Real, unrelated”
(
siliquant/notes/brief-check.md:39). The graph keeps that link with type checked_unrelated. The same
note lists its other links to the lattice tracks as proposals that were not evaluated. Do not present any of
them as a result without a construction.
- Two upstreams of venturi-collars hold no results. Foundation-0/ductricity is a project definition and
Foundation-0/thermal-capture is a research direction. Both say so. venturi-collars inherits a question from
them, not evidence. The graph marks these links
direction.
- The liquid capture fraction has no optimum to find. In funi-frame’s model more capture is always better:
the drive heat needed falls and the surplus rises. There is nothing to optimise there.
- The second-law bound cannot confirm the COP, only limit it. It says where 0.62 is impossible. Whether a
real machine reaches 0.62 at a 58 °C drive needs a manufacturer’s curve.
- The Ledger scale does not fit runtime code. Weft, abios, synbios and the like are tested software, not
research claims. They are left unrated here.
- Lineage by repository over-reaches. Weft builds on Foundation-0/project-asma in its identifiability gate,
a different module from the one optifab uses. For that reason the evidence table covers only the physical
layers, L0 to L3.
-
Only the gate predicate carries over from Weft. Weft’s default radius of 120, its tension bound and its
royalty split have no meaning for a plant. The 12 vectors that test them are out of scope.
- The Terrafab documents are not evidence, and Weft has already audited them. Do not audit them again.
Weft’s digest (
weft/docs/corpus/sources/B-top1.md) records that the latency figures are asserted (line
220), that the benchmark is rigged (line 142), that the Lean proofs they cite do not exist, and that the
gate header neither keeps its own invariant nor bounds a physical quantity (line 227). Weft repaired that
header into the gate it ships (invariants.py:11). optifab uses the idea of one structure and the repaired
gate, and nothing else from those documents.
- This campus has no job for a sub-millisecond loop. Passive isolation holds rack vibration at 17.9% of the
limit and every term of the contract moves over seconds to minutes. A fast loop matters only for active
vibration control or a fabrication machine, and neither exists.
-
No fabrication machine exists anywhere. The “hands” of the Terrafab loop are an idea. The nearest real
inputs are process limits already in the certificates, such as the Fe-SMA activation energy in funi-floors
(0.3227 against a cap of 0.5 kWh/m²).
- The loop’s proposer is not an intelligence, and its gains are not predictions. It is a seeded search on
a three-parameter thermal model, scored on a scenario chosen here. What carries over is the mechanism and
the behaviours in finding 15, not the 0.5%.
- Do not name the gate function
admit in Lean. admit is Lean’s keyword for an unfinished proof, and
the Proven Commons checker rightly flags every use. The function is gate.
- The comparator needs bubblewrap, and the bar check needs every definition a statement uses to be listed
in
bar.toml, constructors and projections included (Verdict.ok, Outcome.verdict, Outcome.remaining).
3. Notes for upstream maintainers
These concern other repositories. Nothing was changed there except the profile fix in item 4.
These three funi-frame notes were implemented in aska-physical/funi-frame#4, merged on 2026-11-24 as v0.1.1.
optifab v0.3.2 follows it: the vendored certificate and the pins are at v0.1.1, findings 1 and 2 are restated
as adopted, and verify.py now checks that the two repositories agree where it used to check that they
differed. The notes are kept below as they were written, for the record.
- funi-frame, compute revenue.
results/certificate.json reports freed_substation_power_MW of 3.06 and
unlocked_annual_revenue_low_M_usd of 76.62, the product of that power and $25M per MW-year
(verify.py:162-163). The power is utility power. The IT load it supports is 2.854 MW if every overhead
grows with load and 2.959 MW if only the aquifer loop does, which is how the verifier models it. The low-end
revenue on that is $71.35M to $73.97M. Suggested change: report the extra IT power, say which kind of MW the
dollar value refers to, and compute the revenue from the matching figure.
- funi-frame, recooling temperature. The sorption COP of 0.62 is a literal (
verify.py:144) with no
temperature attached. Suggested change: carry the drive, recooling and chilled-water temperatures in the
certificate, make the COP depend on them, and add a must-fail control for dry recooling on a hot day.
- funi-frame, controls that compare constants. Must-fail control 10 (
verify.py:181) compares 0.068 with
0.050 and 0.014 with 0.020, and both left-hand values are constants written 25 lines above it
(verify.py:156). It cannot fail. Parts of three others are the same: control 5 tests the literal 0.72
(:99, :176), control 11 tests the literal 0.0 and a ratio of two literals (:152, :182), and control
12 tests the literal 0.0 for water use (:161, :183). The claims may well be right. The verifier does not
test them.
- aska-physical profile. The fibral-rigidity row says pull request 1 awaits human sign-off. That pull
request is merged (
0652052, 2026-11-16). The cfrp-truss row is missing a column separator, which breaks the
table. Both are fixed in the profile change that indexes optifab. That change adds a row, so the profile
lines pinned here move down by one when it merges: run --repin afterwards.
- fibral-rigidity certificate. Its
repository field reads Foundation-0/fibral-rigidity. The repository
is at aska-physical/fibral-rigidity.
- Weft. Its telemetry has no physical input, and its telemetry line carries an unkeyed hash that its
roadmap describes as “integrity against accidents, not authentication”. A plant that takes commands from a
scheduler needs signed messages. Moissanite-Labs/synmerit already defines signed records.
- Weft, one edge case in the gate. With a locked mask, a locked value beyond the float32 range makes
verify_weight_update_safety_ex raise OverflowError instead of returning a rejection
(invariants.py:52-54, reached from the locked-mask check at :69-71). The differential test here found it. plant_gate copies the behaviour
so that the two agree.
- venturi-collars. Its certificate names a 0.150 mW sensor node. At low airflow (1.8 m/s) the collar
harvests 0.104 mW, so that node would need 144% of the harvest. Only the 0.080 mW node is powered there.
4. Artifacts
- verify.py: the derivations, both gates, the plant frame, the loop, the graph and unit checks, 29
must-fail controls.
--formal rebuilds the proofs and replays four ledgers in Lean. Checks are written with
require(), never assert: python3 -O strips assert statements, and until v0.3.0 that let a failing
control write a certificate and exit 0. Control 29 fails if an assert statement comes back. Do not use the
builtin sum() on floats either: its rounding changed in Python 3.12 and made the certificate depend on the
interpreter. Use _sum_sq or an explicit loop. CI runs five Python versions to catch a relapse. And keep
out of the certificate anything that changes when someone else adds a file: a count of scanned files was in
it until v0.3.2, and two unrelated pull requests then left main failing.
- loop.py: the improvement loop. formal/: the Lean project, which now holds
the plant model. formal/tests/oracle.py is its Python copy, and
loop.py calls it.
- tools/propose.py: the proposer’s command line. results/model_run.json
is the recorded run of a language model and results/model_ledger.json its ledger.
- results/ledger.json and results/formal.json: every decision of
the seeded loop, and the record of the last formal run.
- results/certificate.json: the outputs
verify.py must reproduce.
- data/: vendored inputs with hashes, 48 pins, the graph, the unit, and the commit of each of 36
repositories.
- docs/VISION.md, docs/PROPOSALS.md, docs/STRUCTURE.md,
docs/MODEL.md and docs/CONVERGENCE.md. The tables in STRUCTURE.md and
all of CONVERGENCE.md are generated.
- tools/fetch_upstream.py and tools/render_map.py.
To move an element of the unit forward, change its status in data/unit.json. verify.py refuses to report the
loop closed unless every interface is marked checked, and it fails if a repository on the map is neither placed
nor listed as not placed.
To change a pin: edit data/pins.json or data/graph.json, then run
python3 verify.py --upstream ROOT --repin, python3 verify.py --write and python3 tools/render_map.py.
--repin finds each cited text again and records the new commit, file hash and line. It fails if the text is
gone, which is the signal that an upstream claim changed.
5. Next-agent build queue
The larger pieces are written up as eight proposals in docs/PROPOSALS.md, each with an
issue on GitHub. The list below is the working queue, and its first four items are proposals 1, 2 and 7.
Items 1 to 4 close the open places in the loop (docs/STRUCTURE.md, interfaces L1, L2, L5
and L8).
To change the formal project: edit formal/, then run python3 verify.py --formal --write. Any change to a
Lean source, the oracle or a ledger makes must-fail control 24 fail until the formal run is repeated. A change
to the model has to be made twice, in formal/PlantGate.lean and in formal/tests/oracle.py. The differential
tests fail if the two differ. After a change, commit, then rerun the bar check, because it compares the test
record with the committed one.
A recorded run is never edited. To make another, use a new file with tools/propose.py NEW.json new
and add it to RECORDED_RUNS in verify.py. The wording of the rules that show prints was changed after
the two recorded runs, from what the proposers found unclear. A third run would see the new wording and
could be given results/model_lessons_2.md.
- Agree the plant frame with Weft (interface L2, element W1). The 16 slots are defined and tested here.
Weft’s owners decide whether the frame shares their telemetry bus or travels as an abios line. Done when one
fixture file is parsed by both sides. This gives Weft a real temperature in place of its estimate.
- Design the two missing sensors (interface L1, elements N3 and N4). Rack vibration and recooling
temperature each have a certified limit and nothing that measures them.
- A way to shed load, with an energy reading (interface L5). Neither Weft nor Exo can defer or shed compute
on request, and neither measures energy. Until one does, the scheduler side of the contract has nothing to
act on.
- A first fabrication element (interface L8, element F1). Pick one aska-physical process that already has
certified limits, state its gate inputs, and run the gate on them. Fe-SMA activation in funi-floors is the
obvious candidate.
- Done in v0.3.2. Notes 1 and 2 of section 3 are in funi-frame v0.1.1 and optifab’s pins are refreshed.
What is left there is the owner’s: confirm or replace the 30 °C design recooling temperature, and say
whether the compute value is per MW of IT load.
- A year at part load (optifab, with funi-frame issue 2). Run an hourly utilisation trace against the load
floor and the thermal budget. Report hours below the floor and the budget drawn. Share the trace with
funi-frame’s aquifer balance, which injects 84.3 GWh_th a year in one direction.
- Carry the proof over to Weft’s floating-point gate (Weft, Proven-Commons; element R2). The exact gate is
proved in
formal/. What remains is Weft’s open Milestone I.3: a statement relating its float gate to the
exact one, and a reviewer for the specification (proposal 5). The Proven-Commons reviewer list is empty
today, so no project can yet pass bar item 1.
- A second verifier that shares no code (optifab). The Foundation-0 physics rule asks for two. A different
agent, or a different language, should recompute sections 1 to 5 of the model note from the same pins.
- A network of campuses (optifab). v0.3.0 has a first look (section 13 of the model note). The placement
problem is degenerate in the current plant model, because utility power has the same slope at every site.
Before solving anything, give the model a cost that differs by site, or a decision to switch a campus off.
See the status note under proposal 8.
- Replicate the top of the stack (Foundation-0, aska-physical). incentre-lattices’ results sit under 6
repositories of the stack and nhanes-bioimpedance under 5. An independent replication there lifts the most
work. See the evidence table in docs/CONVERGENCE.md.
- Choose a telemetry transport with a parser near the bar (Proven-Commons, element W3). MQTT, CBOR, NTP and
protobuf are all candidates in progress and none is verified. If item 1 picks a transport, prefer one whose
parser is closest to the verified bar.
6. Decisions for a person
- Licence. Added at the owner’s request: PolyForm Noncommercial 1.0.0 for code and CC BY-NC 4.0 for text
and data, so noncommercial use is open and commercial use is reserved. The owner should confirm the
copyright line in NOTICE (“Aska Physical and the optifab contributors”). The sibling aska-physical
repositories still have no licence. Weft’s files are redistributed under Apache-2.0.
- Whether funi-frame should adopt notes 1 to 3. They change published figures.
- Whether the plant gate is a direction worth pursuing. Its arithmetic is now proved, and it has been run
on a model. It has never seen a sensor or a machine.
- Who reviews
formal/SPEC.md. Until a person who did not write it approves it, nothing here may be
called verified. The specification grew in v0.3.0 (the model and seven statements), so its hash changed.
- The defects still open in the model (
formal/SPEC.md). v0.3.1 fixed the objective and the outage margin
and stopped identical proposals being charged. Three things need a design decision: whether a different
design that scores the same should be taken up, whether the statements should require well-formed inputs,
and whether a large move towards safety should be allowed.
- A branch rule. Bar item 7 is open in CI:
main does not require the bar / bar check. Only a repository
admin can add that rule.
- Assumption A-4. The site-dependence of the load floor rests on it. A chiller datasheet would replace it.
- Sign-off. Nothing here counts until a named person reviews it.
7. How this session worked
- Read: every repository listed in docs/CONVERGENCE.md, at the commits listed there, plus
the twelve under “Surveyed and not connected”. The three Terrafab documents named in issue 1 were read in
full, with Weft’s digest of them. Two read-only survey agents located data files and status
lines; every value used here was then re-read directly and is pinned.
- Ran: funi-frame’s
verify.py, which reproduces its certificate (12/12 controls at v0.1.0, 14/14 at v0.1.1). optifab’s own verifier,
offline and against the clones.
- Ran: Weft’s
invariants.py, as the oracle of the differential test. Lean 4.35.0, lake comparator --paranoid
and the Proven Commons bar checker (bar/check.py at mission 7b22e54) on formal/.
- Did not run: the verifiers of the other aska-physical repositories. Their certificates were read as data.
- Reviewed: a second AI agent, given the code and not the conclusions, re-derived the results and tested the
gate against Weft’s. It found that the gate disagreed with Weft’s at floating-point boundaries, that the
compute figure should be a range, that the recooling limit was stated too tightly, that one margin was not
certified upstream, that the lineage depth rule was off by one, and that several controls could not fail.
All of these are fixed in this version. No person has reviewed it.
- Did not read: Moissanite-Labs/exo and the four Proven-Commons protocol repositories. They appear in the graph
as “named only”. Private repositories were not touched.