Written under the group ethos: leave everything the next agent needs so nothing has to be derived twice.

optifab v0.1.0, v0.2.0 and v0.3.0 were prepared by an AI agent on 2026-11-17, and v0.3.1 on 2026-11-24. They are claimed work. No person has reviewed them.

1. What was learned and checked

The aim, stated by the owner and in issue 1, is one physical structure that holds all four organisations’ work, with digital and physical infrastructure as a single unit. docs/STRUCTURE.md is the design of that unit as far as it can be checked today.

The findings are in README.md and derived in docs/MODEL.md. In one line each:

  1. The 3.06 MW of utility power that funi-frame’s plant frees carries 2.85 to 2.96 MW of IT load, depending on how much of the overhead grows with load. Adopted in funi-frame v0.1.1.
  2. The sorption stage needs a heat sink below 41.5 °C at best to reach its claimed COP. funi-frame v0.1.0 had no recooling temperature. v0.1.1 carries the limit and a proposed design value of 30 °C.
  3. The campus stops cooling itself below about 0.56 MW of IT load. A worse wall raises that floor.
  4. The PCM skid is a budget of 2,500 kWh_th that outages and bursts draw on.
  5. The tightest certified margin in the building is the floor punching collar, at 80.1%.
  6. Weft’s gate predicate, rewritten here, passes Weft’s 15 weight-update vectors, agrees with Weft’s own function on 100,000 generated cases, and can take the plant’s budget and margin radius as its inputs.
  7. Six hand-copied values across three repositories agree and are now under test.
  8. The four organisations’ relevant work is one cited graph of 41 repositories and 43 links.
  9. The physical stack is at “claimed” on the Ledger scale, with one preprint.
  10. The contract’s whole state fits the 64-byte frame Weft uses for telemetry.
  11. The Terrafab latency figures hold in direction for the plant’s vibration tones, and the campus as designed does not need a fast loop.
  12. 32 of 41 repositories have a place in the structure. Of the 10 interfaces that would close the loop between structure and intelligence, 4 are checked, and the loop is open in three places.
  13. An exact integer gate and the loop built on it are proved in Lean (eight theorems, six kernels, standard axioms). The Proven Commons bar check passes items 2 to 6. Item 1, a reviewer’s approval, is open.
  14. A loop changed three hardware and two software parameters together under that gate: 45 of 48 proposals admitted, the objective up from 0.914210 to 0.918990, every decision replayed in Lean.
  15. A design that sits exactly on a limit cannot change under this gate, and a proposer with no reserve slows itself.
  16. v0.3.0: the plant model, the bounds, the objective and the step are in Lean beside the gate, and seven more theorems are about designs (fifteen in all, sixteen since v0.3.1). For any proposer the design held stays within the model’s limits and its bounds, its objective never falls, and a margin within the limit is proved to mean three exact inequalities about heat and storage.
  17. A language model proposed through tools/propose.py, seeing only the printed state: 12 proposals, 7 taken up, objective 0.919529, the best a direct search finds possible (the seeded search reached 89.9% of that gain). A second instance of the same model, given the first run’s notes, reached 0.919529 in 5. Two runs, not an experiment. Both runs end with the load_floor margin at 999,215 ppm, 785 from its limit.
  18. 3,007 adversarial proposals could not move the design out of its envelope or past its budget.
  19. Under assumption A-4 the load floor rises steeply with recooling temperature: 0.564 MW at 30 °C, 2.804 MW at 38 °C, no self-cooling at 41 °C. Placement between campuses is degenerate in the current plant model.
  20. v0.3.1 corrected two mistakes in the plant model that an independent read had found: the objective’s outage term and the outage margin, which left out the fixed heat load. Do not carry a recorded run across a change to the model. Only 2 of the 15 proposals recorded against v0.3.0 are decided the same way under v0.3.1, so both runs were made again and the old ones are in results/v0.3.0/.

docs/VISION.md sets these against the vision, part by part.

2. Negative findings. Do not re-derive.

  1. There is no energy data on the digital side. A search of Weft’s runtime, documents and papers, and of weft-loom’s experiments and notes, finds no figure in watts, joules or kWh and no PUE. Weft’s only temperature is a formula of CPU load (weft/runtime/telemetry/host_metrics.py:45). weft-loom lists “energy per adapter write” as a measurement still to make. exo-os quotes small-device power figures from outside sources under the line “Do not trust any mW number without a test.” So tokens per joule, or energy per model update, cannot be computed from anything the four organisations hold today. It has to be measured.
  2. One lattice link is closed, and the others are only proposals. incentre-lattices, fibral-rigidity and siliquant all work with lattices, which suggests a shared result. siliquant checked whether the certificate coefficients of incentre-lattices bear on weight rounding and recorded “Real, unrelated” (siliquant/notes/brief-check.md:39). The graph keeps that link with type checked_unrelated. The same note lists its other links to the lattice tracks as proposals that were not evaluated. Do not present any of them as a result without a construction.
  3. Two upstreams of venturi-collars hold no results. Foundation-0/ductricity is a project definition and Foundation-0/thermal-capture is a research direction. Both say so. venturi-collars inherits a question from them, not evidence. The graph marks these links direction.
  4. The liquid capture fraction has no optimum to find. In funi-frame’s model more capture is always better: the drive heat needed falls and the surplus rises. There is nothing to optimise there.
  5. The second-law bound cannot confirm the COP, only limit it. It says where 0.62 is impossible. Whether a real machine reaches 0.62 at a 58 °C drive needs a manufacturer’s curve.
  6. The Ledger scale does not fit runtime code. Weft, abios, synbios and the like are tested software, not research claims. They are left unrated here.
  7. Lineage by repository over-reaches. Weft builds on Foundation-0/project-asma in its identifiability gate, a different module from the one optifab uses. For that reason the evidence table covers only the physical layers, L0 to L3.
  8. Only the gate predicate carries over from Weft. Weft’s default radius of 120, its tension bound and its royalty split have no meaning for a plant. The 12 vectors that test them are out of scope.

  9. The Terrafab documents are not evidence, and Weft has already audited them. Do not audit them again. Weft’s digest (weft/docs/corpus/sources/B-top1.md) records that the latency figures are asserted (line 220), that the benchmark is rigged (line 142), that the Lean proofs they cite do not exist, and that the gate header neither keeps its own invariant nor bounds a physical quantity (line 227). Weft repaired that header into the gate it ships (invariants.py:11). optifab uses the idea of one structure and the repaired gate, and nothing else from those documents.
  10. This campus has no job for a sub-millisecond loop. Passive isolation holds rack vibration at 17.9% of the limit and every term of the contract moves over seconds to minutes. A fast loop matters only for active vibration control or a fabrication machine, and neither exists.
  11. No fabrication machine exists anywhere. The “hands” of the Terrafab loop are an idea. The nearest real inputs are process limits already in the certificates, such as the Fe-SMA activation energy in funi-floors (0.3227 against a cap of 0.5 kWh/m²).

  12. The loop’s proposer is not an intelligence, and its gains are not predictions. It is a seeded search on a three-parameter thermal model, scored on a scenario chosen here. What carries over is the mechanism and the behaviours in finding 15, not the 0.5%.
  13. Do not name the gate function admit in Lean. admit is Lean’s keyword for an unfinished proof, and the Proven Commons checker rightly flags every use. The function is gate.
  14. The comparator needs bubblewrap, and the bar check needs every definition a statement uses to be listed in bar.toml, constructors and projections included (Verdict.ok, Outcome.verdict, Outcome.remaining).

3. Notes for upstream maintainers

These concern other repositories. Nothing was changed there except the profile fix in item 4.

These three funi-frame notes were implemented in aska-physical/funi-frame#4, merged on 2026-11-24 as v0.1.1. optifab v0.3.2 follows it: the vendored certificate and the pins are at v0.1.1, findings 1 and 2 are restated as adopted, and verify.py now checks that the two repositories agree where it used to check that they differed. The notes are kept below as they were written, for the record.

  1. funi-frame, compute revenue. results/certificate.json reports freed_substation_power_MW of 3.06 and unlocked_annual_revenue_low_M_usd of 76.62, the product of that power and $25M per MW-year (verify.py:162-163). The power is utility power. The IT load it supports is 2.854 MW if every overhead grows with load and 2.959 MW if only the aquifer loop does, which is how the verifier models it. The low-end revenue on that is $71.35M to $73.97M. Suggested change: report the extra IT power, say which kind of MW the dollar value refers to, and compute the revenue from the matching figure.
  2. funi-frame, recooling temperature. The sorption COP of 0.62 is a literal (verify.py:144) with no temperature attached. Suggested change: carry the drive, recooling and chilled-water temperatures in the certificate, make the COP depend on them, and add a must-fail control for dry recooling on a hot day.
  3. funi-frame, controls that compare constants. Must-fail control 10 (verify.py:181) compares 0.068 with 0.050 and 0.014 with 0.020, and both left-hand values are constants written 25 lines above it (verify.py:156). It cannot fail. Parts of three others are the same: control 5 tests the literal 0.72 (:99, :176), control 11 tests the literal 0.0 and a ratio of two literals (:152, :182), and control 12 tests the literal 0.0 for water use (:161, :183). The claims may well be right. The verifier does not test them.
  4. aska-physical profile. The fibral-rigidity row says pull request 1 awaits human sign-off. That pull request is merged (0652052, 2026-11-16). The cfrp-truss row is missing a column separator, which breaks the table. Both are fixed in the profile change that indexes optifab. That change adds a row, so the profile lines pinned here move down by one when it merges: run --repin afterwards.
  5. fibral-rigidity certificate. Its repository field reads Foundation-0/fibral-rigidity. The repository is at aska-physical/fibral-rigidity.
  6. Weft. Its telemetry has no physical input, and its telemetry line carries an unkeyed hash that its roadmap describes as “integrity against accidents, not authentication”. A plant that takes commands from a scheduler needs signed messages. Moissanite-Labs/synmerit already defines signed records.
  7. Weft, one edge case in the gate. With a locked mask, a locked value beyond the float32 range makes verify_weight_update_safety_ex raise OverflowError instead of returning a rejection (invariants.py:52-54, reached from the locked-mask check at :69-71). The differential test here found it. plant_gate copies the behaviour so that the two agree.
  8. venturi-collars. Its certificate names a 0.150 mW sensor node. At low airflow (1.8 m/s) the collar harvests 0.104 mW, so that node would need 144% of the harvest. Only the 0.080 mW node is powered there.

4. Artifacts

To move an element of the unit forward, change its status in data/unit.json. verify.py refuses to report the loop closed unless every interface is marked checked, and it fails if a repository on the map is neither placed nor listed as not placed.

To change a pin: edit data/pins.json or data/graph.json, then run python3 verify.py --upstream ROOT --repin, python3 verify.py --write and python3 tools/render_map.py. --repin finds each cited text again and records the new commit, file hash and line. It fails if the text is gone, which is the signal that an upstream claim changed.

5. Next-agent build queue

The larger pieces are written up as eight proposals in docs/PROPOSALS.md, each with an issue on GitHub. The list below is the working queue, and its first four items are proposals 1, 2 and 7. Items 1 to 4 close the open places in the loop (docs/STRUCTURE.md, interfaces L1, L2, L5 and L8).

To change the formal project: edit formal/, then run python3 verify.py --formal --write. Any change to a Lean source, the oracle or a ledger makes must-fail control 24 fail until the formal run is repeated. A change to the model has to be made twice, in formal/PlantGate.lean and in formal/tests/oracle.py. The differential tests fail if the two differ. After a change, commit, then rerun the bar check, because it compares the test record with the committed one.

A recorded run is never edited. To make another, use a new file with tools/propose.py NEW.json new and add it to RECORDED_RUNS in verify.py. The wording of the rules that show prints was changed after the two recorded runs, from what the proposers found unclear. A third run would see the new wording and could be given results/model_lessons_2.md.

  1. Agree the plant frame with Weft (interface L2, element W1). The 16 slots are defined and tested here. Weft’s owners decide whether the frame shares their telemetry bus or travels as an abios line. Done when one fixture file is parsed by both sides. This gives Weft a real temperature in place of its estimate.
  2. Design the two missing sensors (interface L1, elements N3 and N4). Rack vibration and recooling temperature each have a certified limit and nothing that measures them.
  3. A way to shed load, with an energy reading (interface L5). Neither Weft nor Exo can defer or shed compute on request, and neither measures energy. Until one does, the scheduler side of the contract has nothing to act on.
  4. A first fabrication element (interface L8, element F1). Pick one aska-physical process that already has certified limits, state its gate inputs, and run the gate on them. Fe-SMA activation in funi-floors is the obvious candidate.
  5. Done in v0.3.2. Notes 1 and 2 of section 3 are in funi-frame v0.1.1 and optifab’s pins are refreshed. What is left there is the owner’s: confirm or replace the 30 °C design recooling temperature, and say whether the compute value is per MW of IT load.
  6. A year at part load (optifab, with funi-frame issue 2). Run an hourly utilisation trace against the load floor and the thermal budget. Report hours below the floor and the budget drawn. Share the trace with funi-frame’s aquifer balance, which injects 84.3 GWh_th a year in one direction.
  7. Carry the proof over to Weft’s floating-point gate (Weft, Proven-Commons; element R2). The exact gate is proved in formal/. What remains is Weft’s open Milestone I.3: a statement relating its float gate to the exact one, and a reviewer for the specification (proposal 5). The Proven-Commons reviewer list is empty today, so no project can yet pass bar item 1.
  8. A second verifier that shares no code (optifab). The Foundation-0 physics rule asks for two. A different agent, or a different language, should recompute sections 1 to 5 of the model note from the same pins.
  9. A network of campuses (optifab). v0.3.0 has a first look (section 13 of the model note). The placement problem is degenerate in the current plant model, because utility power has the same slope at every site. Before solving anything, give the model a cost that differs by site, or a decision to switch a campus off. See the status note under proposal 8.
  10. Replicate the top of the stack (Foundation-0, aska-physical). incentre-lattices’ results sit under 6 repositories of the stack and nhanes-bioimpedance under 5. An independent replication there lifts the most work. See the evidence table in docs/CONVERGENCE.md.
  11. Choose a telemetry transport with a parser near the bar (Proven-Commons, element W3). MQTT, CBOR, NTP and protobuf are all candidates in progress and none is verified. If item 1 picks a transport, prefer one whose parser is closest to the verified bar.

6. Decisions for a person

7. How this session worked